If you want an ON if any PWM based valve is more than 1% and OFF if all are set to 0% you can implement that with 3 simple logic functions by setting all in an OR between each other.
This is an example where there are 8 PWM zones, and I'm using:
- one logic block for the first 4
- a second logic block for the next 4
- a third logic block comparing logic blocks 1 and 2 to have a final outcome
First logic, setting in OR for first 4 PWM zones
Second logic, setting in OR for next other 4 PWM zones
Third logic, this will made an OR between the first logic block and the second one.
Communication objects will be set as follow